Top Cable Routing - Huawei UPS5000-A-200K-ST User Manual

Hide thumbs Also See for UPS5000-A-200K-ST:
Table of Contents

Advertisement

UPS5000-A-(200 kVA-800 kVA)
User Manual
● This section describes cable connections when the mains input and bypass
● The figures are for reference only. For more information about the

3.2.14.1 Top Cable Routing

Context
Route cables for the UPS from inside out and from top down.
Figure 3-147 Power distribution module
(1) Battery input
terminal
Procedure
Step 1 Open the front door of the bypass cabinet, and remove the covers of the power
distribution subrack from the bypass cabinet.
Issue 05 (2020-04-27)
NO TICE
input use different power sources. When they use the same power source, there
is no need to remove the copper bars between the mains and bypass input
terminals or connect the bypass input power cable.
recommended cable cross-sectional area and quantity, refer to the section
"Preparing Power Cables" and site requirements.
NO TICE
(2) Mains input
terminal
Copyright © Huawei Digital Power Technologies Co., Ltd.
(3) Output terminal
3 Installation
(4) Bypass input
terminal
178