Bacnet Function Setting - Mitsubishi Electric MELSEC iQ-F Series User Manual

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

BACnet function setting

Set the BACnet functions.
Item
Whether the BACnet functions are used or
not
Network
Network number
information
setting
BACnet device setting
BACnet object setting
BACnet device setting
Set a BACnet device.
Item
Instance No.
Object Name
BACnet standards
I-Am send
Send control
setting
Send I-Am when the
status changes to
Operational
Enable/disable
fixedcycle send
Fixed-cycle send interval
(second)
I-Am response setting
I-Am send setting
Description
Indicates the usage status of the BACnet/IP connection modules in the
external device configuration. (This setting is automatically configured
according to the setting details in the external device configuration.)
Set a BACnet network number.
Page 77 BACnet device setting
Page 78 BACnet object setting
Description
Set a BACnet instance number.
Set a device name. (The same value cannot be set in a module.)
Set the BACnet standards.
Set whether or not to send I-Am only when the device is set to Operational.
Set whether or not to send I-Am when the device status changes to
Operational.
Set whether or not to send I-Am at a fixed-cycle.
Set the interval (second) for sending I-Am. (Available when the enable/
disable fixed-cycle send is set to Enable)
Set how to send I-Am and I-Have for Who-Is and Who-Has.
Set how to send the spontaneous I-Am.
Setting range
• Not used
• Used
(Default: Not used)
0 to 65534
(Default: 0)
Setting range
0 to 4194303
(Default: 0)
16 one-byte alphanumeric
characters maximum
(Default: Blank)
• ANSI/ASHRAE Standard 135-
2016
• ANSI/ASHRAE Standard 135-
2012
• ANSI/ASHRAE Standard 135-
2010
• ANSI/ASHRAE Standard 135-
2004
• IEIEJ-G-0006:2006 Addendum a
(Default: ANSI/ASHRAE Standard
135-2016)
• Send I-Am only at the
Operational status.
• Send I-Am even at other
statuses than Operational.
(Default: Send I-Am only at the
Operational status.)
• Do not send
• Send
(Default: Send)
• Disable
• Enable
(Default: Disable)
1 to 4095
(Default: 60)
• RemoteBroadcast
• GlobalBroadcast
• LocalBroadcast
• Unicast
(Default: LocalBroadcast)
• LocalBroadcast
• GlobalBroadcast
(Default: LocalBroadcast)