Error code
Error name
2C81H
Parameter error
2C82H
Parameter error
2CF0H
CPU module error
2DA0H to
Parameter error
2DA1H
2DA2H
Parameter error
2DA3H
Parameter error
2DA4H
Parameter error
2DA5H
Parameter error
2DA6H
Parameter error
2DA7H
Parameter error
2DA8H
Parameter error
2DA9H to
Parameter error
2DAAH
2DABH
Parameter error
2DB0H
Request data error
3030H
Hardware error
3040H
Update error
3041H
Update error
3042H
Update error
3056H
Socket communication
buffer full
3060H
Parameter error
3061H
Parameter error
3062H
Parameter error
3063H
Parameter error
3064H
Parameter error
3065H
Parameter error
Error details and causes
• A parameter error was detected in the
external device configuration.
• A parameter that is not supported by the
firmware version of the FX5-ENET
module is set.
A parameter error was detected in the
external device configuration.
An error of CPU module was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
A parameter error in external device
configuration was detected.
Request and setting data error
Hardware error
Firmware update file version error
Failure in verification of firmware update file
integrity
Failure in acquisition of firmware update file
The socket communication buffer for
receiving has no space.
The total number of connection is outside
the range.
The station number is outside the range.
The number of occupied stations is outside
the range.
The reserved station specification is outside
the range.
The IP address form is outside the range.
The group number is outside the range.
Action
• Check the external device configuration settings in the FX5-
ENET module parameters.
• Set so that the sum of the number of connections in external
device configuration and the number of settings in the simple
CPU communication settings is 32 or less.
• If the same error is displayed again, the abnormal module may
have a hardware problem. Please consult your local Mitsubishi
representative.
• Check the firmware version of the FX5-ENET module. If a set
parameter is not supported, update the firmware version or
correct the parameter setting.
• Check the external device configuration settings in the FX5-
ENET module parameters.
• If the same error is displayed again, the abnormal module may
have a hardware problem. Please consult your local Mitsubishi
representative.
Check the details of the error of the CPU module with the module
diagnostics of GX Works3, and take measures.
Reexamine and correct the setting of the number of connected
units in external device configuration in the FX5-ENET module
parameters.
Reexamine and correct the setting of the communication method
in external device configuration in the FX5-ENET module
parameters.
Reexamine and correct the setting of the protocol in external
device configuration in the FX5-ENET module parameters.
Reexamine and correct the setting of the model name in external
device configuration in the FX5-ENET module parameters.
Reexamine and correct the setting of the fixed buffer transmission
in external device configuration in the FX5-ENET module
parameters.
Reexamine and correct the setting of the IP address in external
device configuration in the FX5-ENET module parameters.
Reexamine and correct the setting of the IP address (IPv6) in
external device configuration in the FX5-ENET module
parameters.
Reexamine and correct the setting of the existence confirmation in
external device configuration in the FX5-ENET module
parameters.
Check the external device configuration settings in the FX5-ENET
module parameters.
Check the own node port number setting in external device
configuration in the FX5-ENET module parameter.
Check the content of the specified request data.
Please consult your local Mitsubishi representative.
For this update, a PLC applicable to the new version is required.
Please consult your local Mitsubishi representative.
Replace the update file in the SD memory card with the correct
file, and perform update again.
Replace the update file in the SD memory card with the correct
file, and perform update again.
Read out the received data using the dedicated instruction.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
Please consult your local Mitsubishi representative.
10 TROUBLESHOOTING
10.6 List of Error Codes