Number of link points

The number of link points per remote station is 64 points for RX/RY and 32 points for RWr/RWw. ( Page 18 Performance
Specifications)
However, by changing the number of occupied stations, RX/RY can be set to a maximum of 256 points in increments of 64
points and RWr/RWw can be set to a maximum of 128 points in increments of 32 points. For details on the number of
occupied stations (whether or not the number can be changed), refer to the manual for the remote station used.
If the number of link points for the remote station is changed, the assignment range and station number are changed.
(1) Master station
(2) Remote station 1: 1 station occupied
(3) Remote station 2: 2 stations occupied
(4) Remote station 3: 4 stations occupied
The following table lists the number of link points.
Remote
Number of occupied
station
stations
1
1 occupied station
2
2 occupied stations
3
4 occupied stations
Setting the number of link points for a remote station to 2 stations occupied means that two remote stations
are connected. Thus, if the number of link points is increased, the number of connectable remote stations per
network is decreased.
5.2
General-purpose Ethernet Communication
Configuration
For details on the system configuration of the general-purpose Ethernet, refer to the following.
MELSEC iQ-F FX5 User's Manual (Ethernet Communication)
5 SYSTEM CONFIGURATION
62

5.2 General-purpose Ethernet Communication Configuration

(1)
(2)
(3)
RX/RY
Number of
points
64
128
256
(4)
Start
End
0
3F
40
BF
C0
1BF
RWr/RWw
Number of
Start
points
32
0
64
20
128
60
End
1F
5F
DF