Mitsubishi Electric MELSEC iQ-F Series User Manual page 162

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

■E-mail setting storage area clear error code (Un\G4376)
If an e-mail setting clear request is completed with an error, the error code is stored.
• 0: Normal
• Other than 0: Error code
E-mail send function (for diagnostics)
■Error code (Un\G4377)
This area stores an error code at e-mail sending.
• 0: Normal
• Other than 0: Error code
■E-mail sending result (Un\G4378)
This area stores whether the sending was completed successfully or failed for each destination.
(b0 = setting 1, b1 = setting 2..., b9 = setting 10)
• 0: Completed successfully
• 1: Failed
■E-mail sending result (direct specification) (Un\G4379)
This area stores whether the sending was completed successfully or failed for each destination. (Direct specification)
(b0 = setting 1, b1 = setting 2..., b15 = setting 16)
When an error occurs in a communication with the SMTP server or DNS server, FFFFH will be stored.
• 0: Completed successfully
• 1: Failed
■Communication status (Un\G4380)
This area stores the communication status during e-mail sending.
When the execution command of a module function block is turned on and off, the status will be 0000H (Initial state).
• 0000H: Initial state
• 0001H: E-mail sending completed successfully
• 0002H: E-mail sending completed with an error
• 8000H: E-mail sending in progress
■Number of cases in which the function block was completed successfully (Un\G4381)
This area stores the accumulated number of cases in which the e-mail sending function block was completed successfully.
• 0: The instruction has not yet been executed or completed successfully.
• 1 or greater: Number of cases in which the instruction was successfully completed
■Number of cases in which the function block was completed with an error (Un\G4382)
This area stores the accumulated number of cases in which the e-mail sending function block was completed with an error.
• 0: The instruction has not yet been executed or completed with an error.
• 1 or greater: Number of cases in which the instruction was completed with an error
■Number of mails completed successfully (Un\G4383)
This area stores the accumulated number of cases in which a sent e-mail was transferred to the outgoing mail server.
• 0: An e-mail has not yet been sent.
• 1 or greater: Number of cases in which an e-mail was sent successfully
■Number of cases in which an attachment was sent (Un\G4384)
This area stores the accumulated number of cases in which an e-mail with an attachment file was sent.
• 0: An e-mail with an attachment has not yet been sent.
• 1 or greater: Number of cases in which an e-mail an attachment was sent successfully
■Number of cases in which an e-mail was sent to the server (Un\G4385)
This area stores the accumulated number of cases in which an e-mail was sent to the outgoing mail server.
• 0: An e-mail has not yet been sent to the server.
• 1 or greater: Accumulated number of cases in which an e-mail was sent to the server
APPX
160
Appendix 4 Buffer Memory

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5-enetFx5-u-enet-e09r736

Table of Contents