Item
Device restart
Device restart procedure
procedure
setting
Notification destination
network number
Notification destination
IP address
Notification destination
port number
Time synchronization setting
BACnet object setting
Set the instance number, etc. of each object.
For details, refer to  MELSEC iQ-F FX5 User's Manual (BACnet).
Item
Accumulator object setting
AnalogInput object setting
AnalogOutput object setting
AnalogValue object setting
BinaryInput object setting
BinaryOutput object setting
BinaryValue object setting
Multi-stateInput object setting
Multi-stateOutput object setting
7 PARAMETER SETTINGS
78
7.3 Basic Setting
Description
Set the device restart procedure.
Set a network number to which notification is sent at device restart.
(Available when device restart is set to "Support")
Set the IPv4 address to which notification is sent at device restart.
(Available when device restart is set to "Support")
Set a port number to which notification is sent at device restart. (Available
when device restart is set to "Support")
Set the response for receiving wild card.
Description
Set the Accumulator object.
Set AnalogInput object.
Set AnalogOutput object.
Set AnalogValue object.
Set BinaryInput object.
Set BinaryOutput object.
Set BinaryValue object.
Set Multi-state Input object.
Set Multi-state Output object.
Setting range
• Do not support
• Support
(Default: Do not support)
0 to 65534
(Default: 0)
0.0.0.1 to 223.255.255.254
(Default: 192.168.0.254)
0 to 65535
(Default: 47808)
• Ignore
• Output to buffer memory
(Default: Ignore)
Setting range