Mitsubishi Electric MELSEC iQ-F Series User Manual page 160

Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

Diagnostic information display request execution status
■Diagnostic information display request execution status (Un\G4163)
This area stores the execution status of the diagnostic information display following the 'Diagnostic information display
request' (Un\G4162).
• 0: Diagnostic information display not requested
• 1: Diagnostic information display requested
• 2: Diagnostic information display completed
E-mail send function
■TLS setting (Un\G4173)
The enable/disable setting of the TLS setting is stored.
• 0: Disable
• 1: Enable
■Sender mail address (Un\G4174 to Un\G4205)
This area stores the sender mail address (up to 64 characters in ASCII format).
■Sender name (Un\G4206 to Un\G4269)
This area stores the sender name (up to 64 characters in UTF-16 format).
■SMTP server specification method (Un\G4270)
This area stores the SMTP server specification method.
• 0: Host name specification
• 1: IP address specification
■SMTP server name / IP address (Un\G4271 to Un\G4302)
When host name specification is set, the host name (up to 64 characters in ASCII format) is stored.
When IP address specification is set, the IP address (0.0.0.1 to 223.255.255.254) is stored.
■SMTP port number (Un\G4303)
This area stores an SMTP server port number (1 to 65565).
■Authentication method (Un\G4304)
This area stores SMTP authentication method.
• 0: No authentication
• 1: SMTP-AUTH
■User name (Un\G4305 to Un\G4336)
This area stores the user name (in ASCII format).
This area is not available when Authentication method (Un\G4304) is 0 (No authentication).
■Password (Un\G4337 to Un\G4368)
When the account information is set from the buffer memory, the password (in ASCII format) is stored.
When the account information registration is completed, the set value is cleared.
This area is not available when Authentication method (Un\G4304) is 0 (No authentication).
■Certificate verification setting (Un\G4369)
This area stores the setting whether to verify a certificate received from the server.
• 0: Not to verify certificate
• 1: Verify certificate