BACnet function setting

Set the BACnet functions.
Item
Whether the BACnet functions are used or not
Network information
Network number
setting
BACnet device setting
Accumulator object setting
AnalogInput object setting
AnalogOutput object setting
AnalogValue object setting
BinaryInput object setting
BinaryOutput object setting
BinaryValue object setting
Multi-state Input object setting
Multi-state Output object setting
BACnet device setting
Set a BACnet device.
Item
Instance No.
Object Name
BACnet standards
Description
Indicates the usage status of the BACnet/IP connection modules in
the external device configuration. (This setting is automatically
configured according to the setting details in the external device
configuration.)
Set a BACnet network number.
Page 53 BACnet device setting
Page 55 Accumulator object setting
Page 56 AnalogInput object setting
Page 56 AnalogOutput object setting
Page 57 AnalogValue object setting
Page 57 BinaryInput object setting
Page 58 BinaryOutput object setting
Page 59 BinaryValue object setting
Page 60 Multi-state Input object setting
Page 60 Multi-state Output object setting
Description
Set a BACnet instance number.
Set a device name. (The same value cannot be set in a module.)
Set the BACnet standards.
Setting range
• Not used
• Used
(Default: Not used)
0 to 65534
(Default: 0)
Setting range
0 to 4194303
(Default: 0)
16 one-byte alphanumeric
characters maximum
(Default: Empty)
• ANSI/ASHRAE Standard 135-
2016
• ANSI/ASHRAE Standard 135-
2012
• ANSI/ASHRAE Standard 135-
2010
• ANSI/ASHRAE Standard 135-
2004
• IEIEJ-G-0006:2006 Addendum-
a
(Default: ANSI/ASHRAE Standard
135-2016)
6 PARAMETER SETTINGS
6.3 Basic Settings
6
53