ICP DAS USA PIR-130-AC User Manual page 93

Hide thumbs Also See for PIR-130-AC:
Table of Contents

Advertisement

3.10.5 Sub-function 32 (0x20) Read Firmware Version
This sub-function code is used to read the firmware version information for the PIR-130
module.
Request
Byte
Description
00
Address
01
Function Code
02
Sub-function Code
Response
Byte
Description
00
Address
01
Function Code
02
Sub-function Code
03
Major Version
04
Minor Version
05
Build Version
Error Response
Byte
Description
00
Address
01
Function Code
02
Exception Code
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
Length
Value
(in Bytes)
1
1 to 247
1
0x46
1
0x20
Length
Value
(in Bytes)
1
1 to 247
1
0x46
1
0x20
1
0x00 - 0xFF
1
0x00 - 0xFF
1
0x00 - 0xFF
Length
Value
(in Bytes)
1
1 to 247
1
0xC6
1
Refer to the Modbus standard for more
details.
93/93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pir-130-dc

Table of Contents