Specifications - ICP DAS USA PIR-130-AC User Manual

Hide thumbs Also See for PIR-130-AC:
Table of Contents

Advertisement

1.2 Specifications

Model
PIR-130-AC
PIR-130-DC
PIR
Hardware: 8-step Switch-selectable (seconds): 6, 16, 33, 66, 131,
262, 524, 1049
Time-delay
Software: 16-step (seconds): 2, 4, 6, 8, 16, 33, 49, 66, 131, 262,
393, 524, 1049, 2097, 3146, 4194
LUX Control Level :
Hardware: 2 mode (Dawn and dust) / Software: 5-step
Detection Range
Distance: 4 meters Max.
Detection Field of View
360º; Diameter 8 meters Max.
Temperature Sensor
Measuring Range
-25 ~ +100 °C
Fire Alarm
65°C (Programmable)
Resolution
0.0625 °C
Accuracy
±2 °C
Relay Output
Channels
1
Type
Power Relay, Form C
NO: 10A@250VAC
Max. Load Current
NC: 6A@250VAC
Load Wattage
Incandescent Bulb: 1500 W Max.; Fluorescent Lamp 300 W Max.
RS-485 Interface
COM Port
RS-485
Transmission
Distance
Dependent on Baud Rate. For example, 1200 m Max. at 9600 bps.
(m)
Baud Rate (bps)
Softeare:1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Protocol
DCON, Modbus RTU
Node Address
Hardware:160 ~ 191 / Software:1 ~ 255
LED Indicators
LED Indicators
Yes,1 as Power/Communication Indicator. 1 as Alarm Indicator
EMS Protection
ESD (IEC 61000-4-2)
±4 kV Contact for Each Terminal, ±8 kV Air for Random Point
EFT (IEC 61000-4-4)
±4 kV for Power Line
Power Requirements
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
7/93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pir-130-dc

Table of Contents