Aahi(Data) - ICP DAS USA PIR-130-AC User Manual

Hide thumbs Also See for PIR-130-AC:
Table of Contents

Advertisement

2.25 @AAHI(Data)

Description:
This command is used to set the High Alarm limits for a specified module.
Syntax:
@AAHI(Data)[CHKSUM](CR)
@
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
HI
The command to set the High Alarm limits
(Data)
A signed value representing the High Alarm limits in degrees Celsius in the format
xxx.xx. The valid range is +000.00 to +999.99 degrees Celsius.
Response:
Valid Command:
Invalid Command:
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
Examples:
Command: @01HI+086.00
Sets the High Alarm limits for module 01 to +86.00 degrees Celsius, and returns a
response indicating that the command was valid.
Command: @01RH
Reads the high alarm limits for module 01, and returns a response indicating that the
command was valid, with a value of +086.00, which denotes that the High Alarm limits
is +86.0 degrees Celsius.
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
!AA[CHKSUM](CR)
?AA[CHKSUM](CR)
Response:!01
Response: !03+086.00