ICP DAS USA PIR-130-AC User Manual page 24

Hide thumbs Also See for PIR-130-AC:
Table of Contents

Advertisement

Examples:
Command: %0102400600
Changes the address of module 01 to 02. The module returns a response indicating
that the command was valid and includes the new address of the module.
Command: %0101200A00
Attempts to change the Baud Rate of module 01 to 115200 bps, but the module
returns a response indicating that the command was invalid because the INIT DIP
Switch (DIP 4) hasn't been set to the ON position. See Section 1.5 for more details.
Command: %0101200A00
Changes the Baud Rate of module 01 to 115200 bps and the he INIT DIP Switch (DIP 4)
has been set to the ON position. The module returns a response indicating that the
command was valid.
Command: $012
Reads the configuration of module 01 and returns a response indicating that the
command was valid, and showing that the Type Code is set to 40, the Baud Rate is
9600 bps, the Checksum is Disabled and the direction of the counter update is Falling
Edge.
Related Commands:
Section 2.2 $AA2
Related Topics:
Section 1.5 DIP Switch Configuration
Section 1.10 Software Configuration Tables
Notes:
Changes to the address and counter update direction settings take effect immediately after a
valid command is received. Changes to the Baud Rate and Checksum settings take effect on the
next power-on reset.
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
Response: !02
Response: ?01
Response: !01
Response: !01400600
24/93