2.24 @AAEAT

Description:
This command is used to enable the High Alarm function for a specified module and set the
alarm type.
Syntax:
@AAEAT[CHKSUM](CR)
@
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
EA
The command to enable the High Alarm function
T
The Alarm Type:
M: Momentary Alarm
L: Latch Alarm
Response:
Valid Command:
Invalid Command:
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
Examples:
Command:@01EAM
Enables the High Alarm function for module 01 and sets the alarm type to
momentary, and returns a response indicating that the command was valid.
Command:@03DA
Disables the High Alarm function for module 03, and returns a response indicating
that the command was valid.
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
!AA[CHKSUM](CR)
?AA[CHKSUM](CR)
Response:!01
Response:!03
65/93