Aadvv - ICP DAS USA PIR-130-AC User Manual

Hide thumbs Also See for PIR-130-AC:
Table of Contents

Advertisement

2.21 ~AADVV

Description:
This command is used to set the PIR Relay Output signal for a specified module to active or
inactive.
Syntax:
~AADVV[CHKSUM](CR)
~
Delimiter character
AA
The address of the module to be set in hexadecimal format (00 to FF)
D
The command to set the PIR Relay Output to active or inactive
VV
A two-digit hexadecimal value representing the status of the PIR Relay Output
signal. See below for details.
7
Key
OAS
Response:
Valid Command:
Invalid Command:
!
Delimiter character to indicate that the command was valid
?
Delimiter character to indicate that the command was invalid
AA
The address of the responding module in hexadecimal format (00 to FF)
There will be no response if the command syntax is incorrect, there is a communication error, or
there is no module with the specified address.
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
6
5
4
Reserved
Description
Specifies the status of the PIR Relay Output signal
0: An output value of 0 indicates that the relay is inactive
An output value of 1 indicates that the relay is active
1: An output value of 0 indicates that the relay is active
0:
An output value of 1 indicates that the relay is inactive
!AA[CHKSUM](CR)
?AA[CHKSUM](CR)
3
2
1
OAS
0
Reserved
60/93