3.10.3 Sub-function 05 (0x05) Read Communication Settings
This sub-function code is used to read the communication protocol settings for the PIR-130
module.
Request
Byte
Description
00
Address
01
Function Code
02
Sub-function Code
03
Reserved
Response
Byte
Description
00
Address
01
Function Code
02
Sub-function Code
03
Reserved
04
Baud Rate
05 - 07
Reserved
08
Mode
09 - 10
Reserved
Note: This information is the data saved in the EEPROM and will be used for the next power-on
reset. It is NOT the currently used settings.
Baud Rate Settings:
Value
03
Baud Rate
1200
Error Response
Byte
Description
00
Address
01
Function Code
02
Exception Code
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
Length
(in Bytes)
1
1
1
1
Length
(in Bytes)
1
1
1
1
1
3
1
2
04
05
06
2400
4800
9600
Length
(in Bytes)
1
1
1
Value
1 to 247
0x46
0x05
0x00
Value
1 to 247
0x46
0x05
0x00
Refer to the Baud Rate Settings table
below for details.
0x00 0x00 0x00
0: DCON Protocol
1: Modbus RTU Protocol
0x00 0x00
07
08
19200
38400
Value
1 to 247
0xC6
Refer to the Modbus standard for more
details.
09
0A
57600
115200