3.7 06 (0x06) Write Single Register

This function code is used to write a value to address 3xxxx.
Request
Byte
Description
00
Address
01
Function Code
02 - 03
Starting Address
04 - 05
The value to be
written
Response
Byte
Description
00
Address
01
Function Code
02 - 03
Requested Address
04 - 05
Value from the
Requested Address
Error Response
Byte
Description
00
Address
01
Function Code
02
Exception Code
PIR-130-AC/DC User Manual Ver. 1.4.0, 2020/07/28
Length
Value
(in Bytes)
1
1 to 247
1
0x06
2
Refer to the Modbus Address Mapping
Table for details.
2
Length
Value
(in Bytes)
1
1 to 247
1
0x06
2
The value is the same as bytes 02 and 03
of the Request
2
The value is the same as bytes 04 and 05
of the Request
Length
Value
(in Bytes)
1
1 to 247
1
0x86
1
Refer to the Modbus standard for more
details.