2
2.9 Emergency procedure
2.9.1 Overheating of the system
2.9.2 Smell of flue gas
18
If the system overheats and the safety devices fail to operate, proceed as follows:
NOTICE! Do not under any circumstances switch off the main switch or disconnect the
power supply.
❒ Keep all the doors on the boiler closed
❒ Open all mixing valve taps, switch on all pumps.
➥ The Froling heating circuit control takes on this function in automatic operation.
❒ Leave the boiler room and close the door
❒ Open any thermostatic valves on the radiator and ensure sufficient heat
dissipation from the rooms
If the temperature does not drop:
❒ Contact the installer or Froling customer services
DANGER
If you smell flue gas in the boiler room:
Inhaling toxic flue gas can potentially be fatal!
If you smell flue gas in the room where the boiler is installed:
❒ Keep all the doors on the boiler closed
❒ Ventilate the room where the boiler is installed
❒ Close the fire door and doors to living areas
❒ Allow the fire to burn out completely and let the boiler cool
Recommendation: Do not install smoke alarms and carbon monoxide detectors near
the system.