Servicing the system
Servicing the condensing boiler heat exchanger (optional)
5.5.2 Checking the condensation drain
Operating Instructions SP Dual compact | B1500319_en
NOTICE! If the condensation drain is blocked, the condensing boiler heat exchanger
will fill with condensation, thus preventing the flue gas from escaping through the
chimney, which could in turn lead to problems with combustion. For this reason it is
important to check the condensation drain regularly!
At the back of the boiler below the condensing boiler heat exchanger:
❒ Position a suitable container below the siphon to catch the condensation that runs
out
❒ Remove and check the siphon for dirt and deposits
❒ Check the condensation drain up to where it enters the waste water system and
clean if necessary
❒ Ensure that the condensation is continually drained into the waste water system!