Configuration

3.6 SP Ramp Set Up Group

Introduction
Set Point Ramp, Set Point Programs and Set Point Rates can be configured in this group.
A single Setpoint Ramp [SP RAMP] can be configured to occur between the current local
setpoint and a final local setpoint over a time interval of from 1 to 255 minutes.
A Set Point Rate [SPRATE] lets you configure a specific rate of change for any local
setpoint change.
A single Set Point Program [SP PROG] with up to 20 segments can be configured.
For more information on Set Point Rate, Ramp and Programming, see Sections 4.27
through 4.30.
You can start and stop the ramp/program using the
PV Hot Start is a configurable feature and means that, at initialization, the setpoint is set
to the current PV value and the Ramp or Rate or Program then starts from this value.
Added Features not found in other UDC products:
• Up to Four SP Programs rather than one
• 20 segments instead of 12 in each program
• SP Programs 1 and 2 can be linked to give a SP Program of up to 40 segments
• SP Programs 3 and 4 can be linked to give a SP Program of up to 40 segments
• Guaranteed Soak Settings for each Soak Segment
• PID Set selection for each Segment
Function Prompts
ATTENTION
Please note that the configurations used in SP Program #1 for Program End,
Program State, Power Up and Key Reset affect all other SP Programs. For this
reason, Program #1 must always be enabled in order to enable Programs #2, 3
and/or 4.
58
UDC3500 Universal Digital Controller Product Manual
key.
RUN/HOLD
3/07