Levelflex FMP53 PROFIBUS PA

Intermediate height

Navigation
Prerequisite
User entry
Additional information
Table mode
Navigation
Prerequisite
Description
Selection
Additional information
*
Visibility depends on order options or device settings
Endress+Hauser
 Setup → Advanced setup → Linearization → Intermed. height
Linearization type (→  121) has one of the following values:
• Pyramid bottom
• Conical bottom
• Angled bottom
0 to 200 m
H
Intermediate height
The unit is defined in the Distance unit parameter (→  101).
 Setup → Advanced setup → Linearization → Table mode
Linearization type (→  121) = Table
Select editing mode of the linearization table.
• Manual
*
• Semiautomatic
• Clear table
• Sort table
Meaning of the options
• Manual
The level and the associated linearized value are entered manually for each linearization
point.
• Semiautomatic
The level is measured by the device for each linearization point. The associated
linearized value is entered manually.
• Clear table
Deletes the existing linearization table.
• Sort table
Rearranges the linerization points into an ascending order.
H
0%
Operating menu
A0013264
125