5 - CONNECTION TO A CMS

5.2 - Modbus TCP/IP and BACnet IP

Configuring the board
The board is factory fitted. If this is not the case, switch off the controller and insert the board in J13 (entitled BMS card or BMS1) on 
the controller.
Press the button found on the board whilst switching the power to the controller back on. The left-hand LED will start to flash rapidly.
Keep pressing the reset button. After approximately 8 seconds, the left-hand LED (status LED) changes from green to red,
and then starts flashing. At this point, release the button.
Powered up
The board is now initialised to the address 172.16.0.1. You will now need to configure your PC to a fixed IP.
Procedure for Windows 7:
Important: you must have administrator rights to your computer
Go to the Start menu on your PC then Control Panel.
In the Network and Internet section, click the link
View network status and tasks.
36
Status LED
Pushbutton
Earth connector
Release the button
Button pressed
Red
Green
MAC address
Ethernet LED
Button released
Approx 8 s