4.4 - Addressing the pLAN

4.4.1 - Operation
Once the controllers are connected over the pLAN network, the controllers and the terminals must be addressed.
The range of addresses usable is from 1 to 32.
This means that a total of 32 controllers and terminals can be connected over the pLAN. The pLAN cannot work if the same address
is shared by two network elements.
Recommended addressing
It is generally recommended to use a commonly used system of addressing:
The address for the terminals must be equal to the: controller address +16
The shared terminal address must be equal to 16
Please ensure the addressing diagram below is respected:
P01
Trm1
Trm2
Trm3
J14
J15
Controller address: 1
In the following procedures, it is possible that the message "NO LINK" will appear. If this occurs, please repeat the procedure.
: Adr
Priv/Shared
: 17
Pr
: 16
Sh
: None
--OK?
Terminal address: 17
J14
J15
Controller address: 2
Terminal address: 16
P01
: Adr
Priv/Shared
Trm1
: 16
Sh
Trm2
: None
--
Trm3
: None
--OK? No
P02
: Adr
Priv/Shared
Trm1
: 18
Pr
Trm2
: 16
Sh
Trm3
: None
--OK?
Terminal address: 18
J14
Controller
Terminal
address
address
16 (shared)
01
17
02
18
03
19
04
20
05
21
X
X+16
P03
: Adr
Priv/Shared
Trm1
: 19
Pr
Trm2
: 16
Sh
Trm3
: None
--OK?
Terminal address: 19
J15
Controller address: 3
31