Return Flow Of Recirculated Air - bora Professional 3.0 Installation Instructions Manual

Hide thumbs Also See for Professional 3.0:
Table of Contents

Advertisement

The hose connection must be laid in such a way that it is not
subject to deformation, buckling or abrasion.
The stopcock and gas supply pipe connections must be
accessible.
The pressure regulator must correspond to the set gas type
and set gas pressure and must meet local and legal
requirements.
The gas connection hose line must not come into contact with
smoke or the flue outlet of an oven.
The hose line must not come into contact with hot surfaces
on the cooktop or other devices.
Positioning of the gas cooktop with two cooktop
extractors
If the gas cooktop is used in a model with two cooktop extractors, it
is to be installed at the side. If installed between the cooktop
extractors, the pull of air on both sides may affect the flames.
Fig. 4.6
Positioning of the gas cooktop with two cooktop extractors
Air supply for the gas cooktop
To ensure a sufficient air supply, an opening cross-section of at least
50 cm² is required in the front of the kitchen unit, or an opening
cross-section of at least 150 cm² in the plinth area.
u
Make sure that the area below the cooktop has a sufficient air
supply.
1
Fig. 4.7
Air supply at front of the unit
[1]
Air supply via the front of the unit (opening cross-section ≥50 cm²)
[2]
Optional cable protection (shortened)
www.bora.com
Fig. 4.8
[1]
[2]
4.4.6
In the case of recirculation systems, a return flow aperture must be
provided in the kitchen unit to guide the clean recirculated air out of
the unit and back into the room. The return flow aperture can be
created above a shortened plinth. A slatted plinth with at least the
minimum opening cross-section can also be used.
u
u
2
2
Plinth area air supply
Optional cable protection (shortened)
Air supply via the plinth area (opening cross-section ≥150 cm²)

Return flow of recirculated air

Decrease the height of the plinth panel or create corresponding
openings in the plinth.
The cross-section of the return flow aperture must be ≥ 500 cm²
(≥ 1000 cm² in the case of gas appliances) for each cooktop
extractor.