BLJ2/3 to BIC11 or BIC11 to BIC11 (Millennium II Controller)

The cable used in this procedure is:
Rectifier Interface Cable Assembly 847690799 (10 feet) (provided with cabinet)
Refer to Figure 6 - 8 for this procedure.
Step
Connect the Rectifier Interface Cable Assembly from
next cabinet or from any of J1 to J4 of one BIC11 to any of J1 to J4 of the next BIC11.
(J1 to J4 are all common on the BIC11.)
Note:
Remove and discard any resistors
J13
RS485 termination jumper to the 2 - 3 position in the BIC11 of the last cabinet in the system.