Distribution Panels

ED83143-31 Group 1
12" REF
(305mm)
6 Positions for Large
U.S. Circuit Breakers
Large Circuit Breaker Kits
for Groups 1, 4, 101, and 104
Size
Breaker
Comcode
(A)
Positions
108908187
125
108908179
150
108908195
175
108908203
225
108908211
300
108908237
400
108908229
500
108908252
600
108984782
800
*Cables must be the same length and terminate at a
common at each end.
Note
Jumper straps (J1 to J3) on the CLR card shall
be left in the factory default 5 - 12 position for
use with ABB Power Shunt RPM monitoring.
Move these jumper straps to the "Bypass" 1 - 8
position to permit shunt monitoring with non-
ABB equipment. Protection for this wiring
must be provided by the user when these
current-limiting resistors are bypassed.
Figure 8-2: ED83143-31 Group 1 (H469-434/4827/4830 G43/A, G101/A, G102/A, G103/A, or G104/A)
Page 92
© Copyright 2021 ABB. All rights reserved.
Terminal Card (See Note and CLR Card Assignment View)
12" REF
(305mm)
Alarm Card
Wire Ga
(min)
Comcode
1
2
1
1/0
1
2/0
406338665
1
4/0
2
(2) 4/0*
2
(2) 4/0*
405348228
3
(3) 4/0*
3
(3) 4/0*
405348236
4
(4) 4/0*
406021725
405348251
405347923
1200A (800A e/w LVLD) DC Distribution Panel
Connects to
Charge Return Bus
Lugs and Hardware
Std Wire
Lug
Type
Ga
(Class B)
For 1, 2, or 3-position breakers (double-hole load and return lugs)
load
2
rtn
2
load
1/0
rtn
1/0
load
2/0
rtn
2/0
load
--
rtn
--
load
4/0
rtn
4/0
load
--
rtn
--
To DC Loads
847867132 Bolt Kit
Torque to 300 in-lbs (34 Nm)
Flex Wire
Metric
Ga
Wire Size
2
(Class I)
(mm
)
--
35
--
35
--
50
--
50
1/0
70
1/0
70
2/0
--
2/0
--
--
--
--
--
4/0
120
4/0
120
Hardware
Kit
(Grade 2)
847867132