Bic11 (Millennium Ii Controller) - ABB Galaxy Power System Installation Manual

Table of Contents

Advertisement

Bay ID and Shunt Size Configuration (continued)

BIC11 (Millennium II Controller)

Refer to Figure 6 - 11 for this procedure.
Step
Set the Bay ID for the BIC11 by using the S1 (10s place) & S2 (1s place) rotary switches. The cabinet holding the
Millennium II controller should always be ID'd as 01 since the software activates the Bay 01 bay lamp for any
controller alarm. Cabinets without a controller should be ID'd as 02 or higher.
If the shunt to be monitored is at return bus potential instead of hot bus potential, then jumper J15 for Shunt 1 or J16
for Shunt 2 must be moved to the 1-2 position.
Note: Any shunt circuit wired to this BIC11 local shunt circuit must have 100K ohm CLRs (Current Limiting Resistors)
installed at the shunt end of the circuit. These CLRs are provided already by the shop when the shunt circuit
is pre-wired.
If the Software Configured Shunt Size is selected, proceed to the next section on configuration of it using the
Millennium II controller web pages.
Page 52
© Copyright 2021 ABB. All rights reserved.
BIC11 Millennium II Controller
Action
Figure 6 - 11: BIC11 Bay ID and Shunt Size Configuration