Set Rectifier Id - ABB Galaxy Power System Installation Manual

Table of Contents

Advertisement

Initial Power Up of the System (continued)

Set Rectifier ID

Step
Verify the following:
8
·
Green LEDs are illuminated on the rectifier and LVLD and LVBD contactor control boards.
·
The system voltage is 52.08 volts (48V system).
·
The system current is zero.
Set rectifier ID number (choose appropriate procedure):
9
For 595A2 and higher, 595B2 and higher, or 596LT rectifiers:
(GPS 4848)
a.
Depress rectifier power switch in UP position; rectifier ID is displayed.
b.
Hold rectifier power switch in UP position for 5 seconds; the display number will begin to blink.
c.
Release the switch.
d.
Depress and hold the switch for 3 seconds to rapidly advance the ID.
e.
Depress and release repeatedly until the desired ID is reached.
Note – For GPS 4848 rectifier ID's higher than 24, the
25th+ rectifiers must be communicating with the Millennium II controller first before their ID's can be set.
Once the rectifier establishes communication, the ID display can be advanced to the present highest ID
number +1, before returning to ID #1.
f.
Leave switch un-pressed for 10 seconds to save the ID number.
For 595A, or 595B rectifiers:
a.
Depress and hold rectifier power switch in UP position for 5 seconds; the displayed number will begin to
blink.
b.
Depress and release switch until desired number is reached.
c.
When the desired number is reached, continue to hold switch until display stops blinking. The new ID number
is now set. Note: Abandoning this process before the display stops blinking will default the rectifier to the
10
Follow Step 2 to 5 to install the remaining rectifiers, and follow Step 9 (GPS 4848) to set their ID numbers.