Centralized Architecture (Continued)
Remote Voltage Sense and System Shunt for Millennium II Controller when in a
Cabinet with BIC11 Bay Board
These procedures convert the Millennium II Controller to external battery sense (voltage sense at the
central charge and discharge buses) and a single system shunt for load current, when used in a Cabinet
with a
BIC11
Bay Board.
Refer to Figure 6 - 4 for these
Step
Run new wires from the central bus bars. Connect to the BIC11 TB2-10T (RB) and TB2-9T (RG).
Note: If central bus bars have LVBD, sense leads must be on the rectifier side of the contactor.
Move the VSns Jumpers at J20 (Bat Sns) & J21 (DG Sns) from LCL to RMT.
Step
Run new wires (installer-provided) from the system shunt to the BIC11 TB2-8T (SH+) and TB2-3B (SH-). Limit the
resistance of this wiring to 1 ohm maximum.
Typically, this may be accomplished with 22 AWG conductors 25 ft long (1-way) or 20 AWG conductors 45 ft long (1-
way). If the cabling distance to the shunt exceeds these lengths, then
any CLRs (Current Limiting Resistors) in this circuit.
Note: For -48V systems, the SH- connection is to the load side of the shunt (if it is in the return path), and the SH+
Page 41
© Copyright 2021 ABB. All rights reserved.
procedures.
Remote Voltage Sense for Millennium II Controller with BIC11 Bay
System Shunt for Millennium II with BIC11 Bay Board
Action
Action
14
AWG conductors may be used. DO NOT use