Connecting (+) And (-) Conductors - ABB Galaxy Power System Installation Manual

Table of Contents

Advertisement

Battery Connection Panel Options (continued
ED83143-31 G45 with G36

Connecting (+) and (-) Conductors

-48–volt Systems
Battery (-) conductors are connected to the exposed bus bar ends of the battery fuse holders,
contactors, or shunt. Battery (+) conductors are connected to the battery return bus. See Figures 10-2
and 10-3 to locate the battery connection panels and battery return bus. Also see Figures 4 and H3 in
the T83314-30 drawing for additional information.
Page 125
© Copyright 2021 ABB. All rights reserved.
ED83143-31 G31/43
(1) 1200A LVBD – G31
(2) NH3 DIN – each G31
(2) 600A Shunt – each G43
Figure 10-3: H569-4827 Battery Connection Panel Options
)
6000A Battery Shunt included in all GPS
4827 configurations

Advertisement