Safety; Safety Statements - ABB Galaxy Power System Installation Manual

Table of Contents

Advertisement

2. Safety

Safety Statements

Please read and follow all safety instructions and warnings before installing, maintaining, or repairing
a Galaxy Power System. Reference the individual module product manuals for additional safety
statements specific to the modules.
·
The Galaxy Power Systems, GPS 4848/100, GPS 4827, and GPS 4830, are Underwriters Laboratories
(UL) Listed products, evaluated to UL Standard for Safety for Information Technology Equipment -
Safety - Part 1: General Requirements, ANSI/UL60950-1-2014, Second Edition, dated November 10,
2014 and CAN/CSA C22.2 No. 60950-1-07, Second Edition + A2:2014 (MOD), dated October 10, 2014,
UL Subject 1801, Issue Number 2, Power Distribution Centers for Communication Equipment dated
June 12, 2003, and IEC 61204-7, Low voltage power supplies, d.c. output, Annex PS-E. Rectifiers are
individually UL Recognized and/or CSA Certified to ENSI/UL60950-1-2014 and CAN/CSA C22.2 No.
60950-1-07, Second Edition + A2:2014 (MOD), dated October 14, 2014. Rectifiers are also approved
to IEC60950-1/EN60950-1:2006+A11+A1+A12+A2 by an EC Notified Body and have outputs
classified as SELV.
·
Install only in restricted access areas (dedicated equipment rooms, equipment closets, or the like)
in accordance with articles 110-16, 110-17, and 110-18 of the U.S. National Electric Code (NEC), ANSI/
NFPA No. 70, and pursuant to applicable local codes.
·
Rules and Regulations – Follow all national and local rules and regulations when making field
connections.
·
Cable Dress – Dress to avoid damage to the conductors and undue stress on the connectors.
·
Electrical Connection Securing – Torque electrical connections to the values specified on labels or in
the product documentation.
·
Use this equipment in a controlled environment (an area where the humidity is maintained at levels
that cannot cause condensation on the equipment, the contaminating dust is controlled, and the
steady-state ambient temperature is within the range specified).
·
GPS systems are evaluated for use in continuous ambient temperature conditions specific to the
product family. See Appendix A for details listing the rated ambient conditions for each GPS family.
·
Do not install this equipment over combustible surfaces.