Novatech Bitronics M87X Series Manual page 162

Table of Contents

Advertisement

Note: In order to be used for GOOSE publication, the Dataset must be defined under
System\LLN0 as shown in Figure A9.
The second step in publication is defining a GOOSE message, Figure A10. Up to eight
5.
independent GOOSE publications may be defined for each device. Only one is
required for cross-triggering any number of other devices. System\LLN0\gcb01 is used
in this example. All default entries shown in Figure A10 should generally be used in
most cases, but the user must select the dataset defined in step 4, above, from the pull-
down menu in the box Dataset Reference. Then the Configuration Revision must be
incremented to at least 1 (usually incremented automatically by the IED Configurator).
This Revision number must match the corresponding GOOSE subscription settings on
all the other inter-triggered IEDs on the network (see step 7, below).
ML0021
Figure A 8
Figure A 9
August 15, 2018
146
Copyright 2018 Bitronics, LLC

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents