of:
192.168.0.254 / 255.255.255.0 / 192.168.0.1
and for OSI with an NSAP of:
49 00 01 42 49 09 01 01
The 70 Series IEDs use the following port numbers for each type of protocol:
PROTOCOL
DNP
FTP (recommend passive mode)
Modbus
MMS (UCA & 61850)
SMTP (electronic mail)
SNTP (network time sync)
Telnet
8.2 Features
10/100 Megabit auto-negotiable copper interface with RJ-45 connector (P1x, E1, E3).
Optional 10 Megabit fiber optic interface with ST connector for 62/125um glass fiber
(P11)
Optional 100 Megabit fiber optic interface with ST connector for 62/125um glass fiber
(P12 and E3)
Compliant to IEEE 802.3-1996 and IEEE 802.3u-1995
Compliant to UCA Utility Initiative Statement Of Work Rev 7
Compliant with IEC61850 Part 3 and Part 8-1 TCP/IP T-profile physical layer option 1
(copper)
Compliant with IEC61850 Part 3 and Part 8-1 TCP/IP T-profile physical layer option 2
(100 Mb fiber - P12 only).
Fully automatic port switching with manual override capability
Six indicator LEDs (P1x)/Two indicator LEDs (E1, E3)
Protected, utility-grade copper interface
8.3 Specifications (For P1x Modules Unless Otherwise Noted)
Ethernet Connection:
(-P10/ E1)
10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-TX)
(-P11)
10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-TX)
820 nm 10 Mb fiber-optic port (10BASE-FL).
(-P12/E3)
10/100 Megabit (Mb) RJ45 (copper) interface (10BASE-T and 100BASE-TX)
1300 nm 100 Mb fiber-optic port (100BASE-FX).
ML0021
August 15, 2018
PORT NUMBER
20000 (TCP, UDP)
20, 21 (TCP)
502 (TCP)
102 (TCP)
25 (TCP)
123 (UDP)
23 (TCP)
109
Copyright 2018 Bitronics, LLC