Signal Input Module S10 - S12, S1C (M871), S13 - S17, S2C (M872); Introduction; Features - Novatech Bitronics M87X Series Manual

Table of Contents

Advertisement

7.0 SIGNAL INPUT MODULE S10 - S12, S1C (M871), S13 - S17, S2C (M872)

7.1 Introduction

The Signal Input Module provides the terminal blocks, current transformers, and voltage
input dividers for the signals to be measured. Compensation for normal variations in input
circuits is achieved by storing calibration constants in non-volatile memory (EEPROM),
which resides on the Signal Input Board. These constants are factory-programmed to
provide identical signal gain (attenuation) in each of the 14 signal input paths. Checksums
are incorporated into the EEPROM, which are read periodically by the microcontroller to
check the integrity of the calibration constants.

7.2 Features

Utility-grade current input terminal block with 10-32 studs (M871) or 8-32 screws
(M872)
Current shunts are #12 AWG SIS, 600V wire, crimped ring-lugs with brazed seams
Options for split-core CTs (external)
Voltage measurements to 424V rms line-to-neutral (730V rms line-to-line)
7kV, 7.5MΩ input resistors on voltage inputs.
Removable voltage input terminal block accepts bare wire or terminal lugs.
Non-volatile memory backup of CT/VT calibration data
ML0021
August 15, 2018
86
Copyright 2018 Bitronics, LLC

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents