UPS PARALLELED ON THE SAME BATTERY

NOTE !
A Parallel System with a Common Battery for two or more UPS (max. 4 units), requires
a particular installation and adequate setting of some parameters, (accessible only
through password), and can therefore only be done by a GE QUALIFIED ENGINEER.
Usually each UPS Unit runs with its own Battery.
In case of parallel units running with a Common Battery (max. 4 UPS - see Fig. 4.4-1), the sharing circuit
between the individual UPS is integrated in the communication bus of the system in order to assure an
equal sharing of the Rectifiers output currents.
Fig. 4.4-1 Diagram RPA system with UPS on Common Battery
Pay attention to the following recommendations:
The units delivered for this functioning mode needs special parameters setting, so they must be
prepared in advance before the installation.
The installation must be performed only with the UPS system completely shut down.
The AC Rectifiers input power (4) must be the same, with clockwise phase rotation for each unit.
Each Rectifier must be set for the same floating DC voltage and the same Battery current limitation.
It is mandatory to install the fuses / MCB (6) on each line connecting the Rectifiers to the common
Battery for maintenance / safety reasons (see Installation Guide to Section 4.8.2).
In case a unit must be powered down for maintenance, switch-OFF the concerned unit before open
the DC fuses / MCB on the Battery line (6).
It is recommended to connect an external NO free contact "Battery Fuses" to the UPS and to enable
the function by setting the parameter (see Section 9.1).
If an emergency generator set supplies the UPS, and the free contact "Generator ON" is connected
to the Customer Interface, connect a separate NO free contact on each parallel unit.
The parameters enabling the Battery test, both manual and automatic, must be set in the same
mode on all the units sharing a Common Battery.
Do not connect the temperature sensor for automatic battery floating voltage compensation.
Do not enable the function Boost charge.
Modifications reserved
GE_UPS_USM_TLE_SUL_40K_M15_1US_V010.docx
1 –
Rectifier
2 –
Inverter
3 –
Automatic Bypass
4 –
Utility Input
5 –
Load Bus Bar
6 –
External Battery Fuse
7 –
External Battery
Page 19/90