GE FGC TLE Series Manual page 498

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

3. Perform the command "Module shutdown" on the
Unit to separate only when the symbol Q1 in the
Synoptic Diagram is shown open.
Perform the command "Module shutdown" through the
screen: Commands 1 / Module shutdown / Shutdown.
Synoptic diagram of the unit to separate
4. Disconnect the Battery on the Unit to separate by opening the "External Battery Protections".
Press "MUTE" key to reset Acoustical Alarm. LED ALARM remains lit.
Synoptic diagram of the unit to separate
NOTE !
Before performing the next procedure (5) wait 5 minutes for DC-Link Capacitors
discharge.
Use the MEASURES/Rectifier screen to ensure that the DC-link1 and DC-link 2 voltage
has reached 10Vdc.
5. Disconnect the Utility supply on the Unit to separate.
LCD display is Off
Synoptic diagram of the unit to separate
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.
NOTE !
For any further intervention contact nearest Service Center.
Modifications reserved
GE_UPS_USM_TLE_SUL_M62_1M0_2US_V010.docx
Critical Power
END OF PROCEDURE
Synoptic diagram of other units
Synoptic diagram of other units
Synoptic diagram of other units
User Manual TLE Series 625 - 750 - 1000 UL S2
Page 81/92