4.5

VENTILATION AND COOLING

Fig. 4.5-1 Installation on plain floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
19.7" (500mm) of air clearance MUST BE LEFT from the top of the UPS for a sufficient
exhausted air exchange, proper cooling, service access and safety.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
Contact your GE Service Center for appropriate solutions.
The below table indicates the heat dissipation at full Load at PF = 1 and charged Battery, up to 3280 ft
(1000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
UPS model
TLE Series 160
20137 BTU/hr
TLE Series 200 25256 BTU/hr
TLE Series 225
27986 BTU/hr
TLE Series 250
31741 BTU/hr
TLE Series 300 32765 BTU/hr
TLE Series 400 48123 BTU/hr
TLE Series 500 63823 BTU/hr
NOTE !
Even when eBoost™ Operating Mode option is available, the ventilation and cooling
system shall be rated as for operation in VFI mode.
Modifications reserved
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
Critical Power
Losses
VFI
PF = 1
5.9 kW
6826 BTU/hr
7.4 kW
8532 BTU/hr
8.2 kW
10922 BTU/hr
9.3 kW
10239 BTU/hr
9.6 kW
12799 BTU/hr
14.1 kW
18089 BTU/hr
18.7 kW
20819 BTU/hr
Fig. 4.5-2 Installation on raised floor
eBoost™ (option)
PF = 1
2.0 kW
2.5 kW
3.2 kW
3.0 kW
3.8 kW
5.3 kW
6.1 kW
Installation Guide TLE Series 160 - 500 UL S2B
Cooling air flow
VFI
PF = 1
1013 CFM
1721 m
3
1270 CFM
2158 m
3
1408 CFM
2392 m
3
1597 CFM
2713 m
3
1648 CFM
2800 m
3
2421 CFM
4113 m
3
3210 CFM
5454 m
3
Page 21/60
/h
/h
/h
/h
/h
/h
/h