GE FGC TLE Series Manual page 9

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

TLE Series Power Capability (Cont.)
BYPASS
Voltage limits for inverter/
bypass load transfers
Overload on bypass
Primary components
INTERFACING
Standard interfacing features
PHYSICAL DATA
Weights
Floor loading
Dimensions (WxDxH)
9
+/- 10% (adjustable)
198A continuous - 270 for 1 minute - up to 3000A for 10ms, non repetitiive
Static switch (SCR) on bypass
Electromechanic contactors (backfeed protection) on bypass and inverter
RS232 serial port, EPO, Customer Interface board, 3-ph SNMP/MODBUS/WEB plug-in Adapter,
Black Box for standard intelligent Diagnostics
849 lbs / 385 Kg
152 lbs/sq.ft / 742 Kg/m
2
23.62 x 34.06 x 64.17 inches / 600 x 865 x 1630 mm
992 lbs / 450 Kg
178 lbs/sq.ft / 867 Kg/m
2
LP33 Series II UPS
1147 lbs / 520 Kg
205 lbs/sq.ft / 1002 Kg/m
2
|