GE FGC TLE Series Manual page 200

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

Fixing of the UPS cabinet TLE Series 160 - 500 on the floor
The UPS cabinet is free
standing
and
normally
does not require to be
bolted to the floor.
The UPS cabinet can be
fixed however to the floor
by bolting it with the
supporting blocks to the
floor.
2.13 " / 54 mm
2.37 " / 60 mm
2.37 " / 60 mm
Fig. 4.4.1-7 TLE Series 160 - 220 - 225 - 250 UPS cabinet floor fixing points
2.13 " / 54 mm
FRONTAL SIDE
27.56 " / 700 mm
2.37 " / 60 mm
Modifications reserved
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
FRONTAL SIDE
27.56 " / 700 mm
44.10 " / 1120 mm
3.94 " / 100 mm
63.78 " / 1620 mm
Fig. 4.4.1-8 TLE Series 300 - 400 - 500 UPS cabinet floor fixing points
Critical Power
Fig. 4.4.1.6 Fixing of the UPS cabinet on the floor
14.18" / 360mm
27.56 " / 700 mm
TLES_UL_225-250_S1_UPS fixing_01
TLES_UL_400-500_S1_UPS fixing_02
2.37 " / 60 mm
Installation Guide TLE Series 160 - 500 UL S2B
Page 19/60