GE FGC TLE Series Manual page 73

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

BATTERY
Battery type
Float voltage at 68°F / 20°C
Number of cells
Min. discharge voltage (programmable)
Recharge time
"Battery to earth" fault detection
Automatic and manual battery test
Common battery in parallel system
Battery power data
DC power at full load & PF=0.8 lag. / PF=1
Maximum discharge current (1.65V/cell)
Matching battery cabinets
INVERTER
Nominal output apparent power from PF=0.6 lag. to 0.9 lead.
Nominal output active power
Nominal output voltage (on site programmable)
Inverter bridge
Output waveform
Output voltage tolerance:
- static .....................................................................................................
- dynamic (at load step 0 – 100 – 0%) ......................................
- dynamic (at load step 0 – 50 – 0%) .........................................
- recovery time to +/-1% ................................................................
- output voltage THD for 100% linear load ............................
- output voltage THD for 100% non-linear load (EN 62040)
Output voltage tolerance at 100% unbalanced load (Ph-N)
Output frequency
Output frequency tolerance:
- free-running ......................................................................................
- with mains synchronization adjustable to ...........................
Phase displacement:
- at 100% balanced load ................................................................
- at 100% unbalanced load ...........................................................
Overload capability (at 77°F / 25°C ambient temperature)
Short-circuit characteristic
MCCB clearance capability (selectivity)
Crest factor
BYPASS
Input connection
Primary components
Voltage limits for inverter/bypass load transfers
Overload on bypass
INTERFACING
RS232 serial port
EPO - EMERGENCY POWER OFF
Customer Interface board
6 programmable signalling voltage-free contacts ..............
(available on block terminals)
Input signals ..........................................................................................
3-ph SNMP/MODBUS/WEB plug-in Adapter
Black Box
Note: all indicated values are typical. Variations may be found from one unit to another.
Modifications reserved
GE_UPS_TDS_TLE_SUL_40K_M15_US_1US_V010.docx
Critical Power
Valve regulated lead-acid (VRLA)-standard, Vented lead-acid, wet battery and NiCd
545V (dependent on the number of cells)
VRLA at 2.27V/cell: 240 cells
Vented lead acid at 2.23V/cell
396V
<5 hours up to 90% of battery capacity
Standard
Standard
Up to 4 units
kW
40
50
kW
33.6/42.0
42.0/52.5
Amps
85/106
106/133
See option features on page 5 and 7
40 – 50 – 80 – 100 – 120 - 150 kW
40 – 50 – 80 – 100 – 120 - 150 kW
3 x 480V + N
Advanced Neutral Point Clamped three level IGBT technology
Sine wave
+/- 1%
+/- 3%
+/- 2%
<5 ms
<3%
<5%
+/- 3%
60 Hz
+/- 0.1%
+/- 4%
120°: +/- 1%
120°: +/- 3%
105% continuous, 110% - 10 minutes, 125% - 1 minute, 150% - 30 seconds
Electronic short-circuit protection, current limit to:
2.2 times In for 100ms between phase/phase and phase/N/PE
20% In within 5-10ms (with MCCB class C or magn. trip at max. 10In)
>3:1
Separate for rectifier and bypass input or common to the rectifier input
- Static switch (SCR) on bypass
- Electro mechanic contactors (back feed protection) on bypass and
inverter
+/- 10% (adjustable)
198A continuous - 270A for 1 minute – up to 3000A for 10ms, non repetitive
Standard
Standard
Standard
- Standard information for easy integration and signaling
- 27 user settable signals
- GEN ON (emergency power supply ON, n/o contact, customer supplied)
- 1 auxiliary signal, with settable functionality
Standard
Standard Intelligent Diagnostic
80
100
120
67.3/84.1
84.1/105.1
100.9/126.1 126.1/157.6
170/212
212/265
255/318
Technical Data Sheet TLE Scalable Series 40 - 150 UL S1
150
318/398
Page 4/7