40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

TECHNICAL DATA SHEET - 160 / 200 / 225 / 250 kW UL LISTED
Enclosure
Type
Safety
Cooling
Color
Installation
Rigging
Mounting
Installation and maintenance access
Conduit Entry
Standards
Electrostatic discharge immunity
Configuration
Standard
Optional
Fault current rating
RECTIFIER
Configuration
Input
Voltage
Frequency
Harmonic Current Distortion
Power Factor (Typical)
Inrush current
Power walk-in
Output Voltage Tolerance
DC ripple voltage
DC ripple current
UPS RATING vs. CURRENT LIMITS
Nominal input (100% load)
(1 PF load, fully chrg'd bat.)
Maximum input (100% load)
(1 PF load, max. chrg current)
Max. charge current
3
TLE Series UPS 160/200/225/250 Technical Datasheet
Indoor (IP20) and NEMA PE 1
Internal dead front construction
Forced Air
Black (RAL 9005)
Suitable for handling by forklift
Floor mounting holes provided
Front access required for normal maintenance
Top and Bottom standard
ETL Listed to UL 1778, ANSI C62.41b
4kV contact / 8kV air discharge
Stand-alone
Redundant Parallel Architecture (RPA) - up to 6 modules may be paralleled in any combination for
redundancy or capacity
UPS is designed for installation in an electrical system up to 65kA
Three phases rectifier bridge with three level IGBT technology
480VAC, 3-phase, 4 wire + ground OR 3 wire + ground
(+/- 15% without battery discharge)
60Hz, +/-10% (54-66Hz)
<5%
0.99 lagging
Limited by soft-start circuit
30 seconds (Adjustable)
+/- 1%
+/- 1%
Max. 5% of battery capacity expressed in amps
160 kVA/kW
Current[A]:
201.6
kVA
167.6
kW
165.9
Current[A]:
228.9
kVA
190.3
kW
188.4
A:
45
GECriticalPower.com
200 kVA/kW
225 kVA/kW
251.7
283.5
209.3
235.7
207.2
233.3
279.0
310.2
232.0
257.9
229.7
255.3
45
45
250 kVA/kW
315.0
261.9
259.2
341.7
284.1
281.2
45