4.9.5 Use of TLE Series 625 - 750 - 1000 in eBoost™ Operation Mode
NOTE !
For systems intended to be operated in eBoost™ Operation Mode, the installation
shall be protected with suitable surge protection devices (SPDs) on the AC bus
feeding the UPSs.
Please contact your Service Center for more information.
NOTE !
In eBoost
load and combined with the load current it contributes to the UPS input
characteristic.
As the inverter output filter exhibits a predominantly capacitive characteristic, it
may provide some degree of reactive power compensation when combined with
lagging power factor loads.
Conversely, depending on the load type and level, the UPS input characteristic
may exhibit a leading power factor in eBoost
Please contact your Service Center for more information.
NOTE !
If an emergency generator set supplies the UPS in case of Utility Failure and the
system is intended to be operated in eBoost™ Operation Mode, eBoost operation
shall be prevented during generator operation.
This can be accomplished by either installing a "GENERATOR ON" signal (refer to
Section 5.2.5) or an "eBoost/IEMi CONTROL" signal (refer to Section 5.2.7).
Please contact your Service Center for more information.
Modifications reserved
GE_UPS_ISG_TLE_SUL_M62_1M0_2US_V010.docx
Critical Power
Operation Mode the inverter output filter is placed in parallel with the
TM
Operation Mode.
TM
Installation Guide TLE Series 625 - 750 - 1000 UL S2