Ventilation And Cooling - GE FGC TLE Series Manual

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

4.5

VENTILATION AND COOLING

Fig. 4.5-1 Installation on plain floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Air inlets for UPS ventilation are located on the front of the UPS, while air outlets are on top of the
cabinet.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Do not put anything on the top of the cabinet.
19.7" (500mm) of air clearance MUST BE LEFT from the top of the UPS for a sufficient
exhausted air exchange, proper cooling, service access and safety.
Air filtering systems could be required when the UPS operates in a dirty environment.
In order to prevent overheating of the UPS, the available air intake flow rate must exceed the total air
exhaust flow rate requirement of the UPS system.
Contact your Dealer or the nearest Service Center for appropriate solutions.
The below table indicates the heat dissipation at full Load at PF = 1 and charged Battery, up to 3280 ft
(1000 m) altitude, for cooling air 77°F (25°C) to 86°F (30°C).
UPS model
TLE Series 625
TLE Series 750
TLE Series 1000
NOTE !
Even when eBoost™ Operating Mode option is available, the ventilation and cooling
system shall be rated as for operation in VFI mode.
Modifications reserved
GE_UPS_ISG_TLE_SUL_M62_1M0_2US_V010.docx
Critical Power
Losses
VFI
PF = 1
94260 BTU / hr
24.7 kW
98325 BTU / hr
28.8 kW
134783 BTU / hr
39.5 kW
Fig. 4.5-2 Installation on raised floor
eBoost™ (option)
PF = 1
30288 BTU / hr
8.9 kW
31082 BTU / hr
9.1 kW
37951 BTU / hr
11.1 kW
Installation Guide TLE Series 625 - 750 - 1000 UL S2
Cooling air flow
VFI
PF = 1
4240 CFM
7204 m
/h
3
4944 CFM
8400 m
/h
3
6780 CFM
11520 m
/h
3
Page 22/69

Advertisement

Table of Contents
loading

Table of Contents