4.7.3 Data for Input/output and battery over current protection and wire sizing
NOTE !
•
Please read the safety precautions at the front of this guide carefully, and
thoroughly review the battery manufacturers installation and maintenance
manual before connecting the batteries to the UPS.
•
Remote battery cabinet is external and not provided with UPS.
•
For Battery and AC input and output circuits the disconnect device is not
provided inside the UPS. It shall be part of the building installation.
•
Protect Battery and AC input and output circuits with an appropriate UL489
Branch Circuit Protection (DC fuse or circuit breaker), using the current data in
the chart below.
•
Minimum battery cable requirement is based on the current data below.
•
The maximum available fault current from the battery supply is: 20kA.
•
The minimum breaker voltage rating is 540V.
These maximum and nominal ratings should be considered when choosing the appropriate AC
NEC (National Electric Code) Section 210-20 (A) rules must be applied.
DC current rating is the nominal battery discharge current which the UPS allows.
UPS rating
Nom.
TLE Series 160
202 A
TLE Series 200
252 A
TLE Series 225
285 A
TLE Series 250
315 A
TLE Series 300
378 A
TLE Series 400
504 A
TLE Series 500
630 A
Modifications reserved
GE_UPS_ISG_TLE_SUL_M16_M50_2bU_V010.docx
The AC values below are current ratings per phase.
over current protection device.
(See Fig. 4.7.1-1 and 4.7.1.2)
AC Input Rectifier
F1
Max.
230 A
285 A
310 A
345 A
430 A
555 A
690 A
Critical Power
AC Input Bypass
F2
Nom.
193 A
202 A
240 A
252 A
271 A
285 A
301 A
315 A
361 A
378 A
481 A
504 A
601 A
630 A
AC Input
DC Input
F3
Max.
230 A
392 A
285 A
488 A
310 A
545 A
345 A
605 A
430
727 A
569 A
968 A
690 A
1210 A
Installation Guide TLE Series 160 - 500 UL S2B
F4
Page 26/60