GE FGC TLE Series Manual page 278

40-150 kva/kw, 480 vac three phase highly efficient and scalable
Table of Contents

Advertisement

Code
BOOSTER/BATTERY CHARGER
4143
CURRENT MAX
4146
4TH LEG DRIVER FAILURE
4147
BATTERY CHARGER DRIVER FAILURE
4150
BOOSTER OVERTEMPERATURE
4151
4TH LEG OVERTEMPERATURE
4301
INVERTER FUSES
4304
K7 CLOSING FAILURE
4305
K7 OPENING FAILURE
INVERTER TRANSFORMER
4307
OVERTEMPERATURE
4308
DC FUSES FAILURE
4309
DRIVER FAILURE
4310
IGBT RECTIFIER DRIVER FAILURE
4311
BOOSTER DRIVER FAILURE
INVERTER VOLTAGE OUT
4312
OF TOLERANCE
4320
ISMAX DETECTION
4321
HIGH CURRENT SHARING
4340
INVERTER CONTROL FAILURE
Modifications reserved
GE_UPS_USM_TLE_SUL_M16_M50_2bU_V010.docx
Critical Power
Alarm
Description
Detection
of
maximum
booster/battery charger.
The Booster/Battery charger and Inverter will switch
off for protection purposes.
The Booster's driver indicates the presence of a
defect which switches the power off.
The Battery charger driver indicates a defect,
switching it off.
The temperature of the booster bridge exceeds the
machine's set limit or the coil's sensor is on.
The temperature of the 4
machine's set limit.
The alarm signals an Inverter outlet fuses fault,
causing it to switch off immediately.
It may only be manually switched on after the alarm
has ceased.
K7 not closed despite a closing command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
K7 not open despite an opening command.
Signaled by auxiliary contact.
Load will be supplied by Utility.
The temperature sensor of the Inverter Transformer
indicates overtemperature.
Elapsed "stop operation" time, Inverter shut-down.
With Utility OK, Load is transferred on Utility.
Blown input DC fuse(s) F1 of the Inverter.
Inverter cannot be started as long as present.
An abnormal condition has been detected on one or
more power modules of the Inverter (temperature or
overcurrent).
Inverter shut-down and cannot be started as long as
the alarm is present.
Indicates a failure on the driver board or the Rectifier
IGBT bridge.
The Rectifier is shut-down.
Driver Booster error signal.
Inverter Output Voltage is out of the tolerances (±
10%).
Inverter is switched OFF.
Detection of Inverter Bridge (Is) current limit causing
the Inverter OFF and automatic re-start.
After 3 times the Inverter switches-Off, and it can be
restarted manually.
A high exchange current value is detected between
the UPS of the Parallel System.
The "Slave" oscillator is not in synchronized with the
Master; thus causing the shut-down of its Inverter.
If after a restart the condition remains, the LED
inside the Inverter symbol on the panel will not light
up, indicating that this Inverter cannot supply the
Load anymore.
current
in
leg's bridge exceeds the
th
Page 37/91
User Manual TLE Series 160 - 500 UL S2B
the

Advertisement

Table of Contents
loading

Table of Contents