4.7.2 FSDs monitoring loop (terminals 26-27)
The FSDs monitoring loop is provided by the RESTART input. (see chapter 4.8.2).
The Normally Closed contacts of the two FSDs relays K1 and K2 or FF-SRE extension
module must be connected in series between terminals 26-27 to check correct operation of
the FSDs each time the OSDs outputs switch. If a failure of the FSDs relays K1 and K2 or
FF-SRE extension module is detected, the OSDs outputs remain open until the failure is
removed.
IMPROPER EXTERNAL SAFETY RELAYS PERFORMANCE
Use two independent stop circuit safety relays K1 and K2 with mechanically linked
contacts (such as GE CR120 BP Machine Tool Relay or Telemecanique CA3-KN31BD3 or
CA3-DN31BD relay) or FF-SRE extension module to reliably detect a welded contact.
Always use the FSD monitoring loop to check correct operation of relays K1 and K2.
Failure to comply with these instructions could result in death or serious injury
Figure 4.12 : Connection of the FSDs monitoring loop
+24Vdc
2.5A
P/B3
K1
K2
32
27
26
+24V
OUTPUT
RESTART
FF-SRM
2
Machine
control
K2
circuitry
K1
0 V
Features
RESTART input
Type
voltage presence and without reference potential
Dynamic signal
pic of 50 mA min.
NC contacts
50 Ohms max. resistance
Protections
galvanic insulation : 500 Vdc
62
FSD
K1 *
25
OSD1
OSD2
8
FSD
K2 *
107004-15 EN FR26 ROW 0899 Printed in France