ST Connector with the Cable-to-cable Connector

1. Remove protective caps on the cable-to-cable connector and the optical fiber cable ends.
Keep the protective caps for future use.
2. Engage the ST fiber optic connector onto one side of the cable-to-cable connector. Turn
the ST connector until the cable-to-cable receptacle tabs are aligned with the ST
connector slots. Further engage the ST connector and turn it until secured.

Fiber Optic Cable Connection to the Connecting Box

CONNECTING BOX DAMAGE
• Install one fiber optic cable per cable gland.
• Properly install the sleeve tube into the cable gland and hand tighten the plastic cap screw
onto the cable gland to ensure proper cable sealing.
Failure to comply with these instructions will result in product damage.
1. Remove the plastic cap screw from the cable gland to gain access to the rubber seal
inside.
2. Remove the precut hole from the rubber seal.
3. Remove protective caps on the cable-to-cable connector and the optical fiber cable ends.
Keep the protective caps for future use.
4. Slide one ST connector of the fiber optic cable through the plastic cap screw and the
rubber seal inside the cable gland.
5. Repeat step 4 with the second ST connector.
6. Repeat steps 1 through 5 for all the safety mat optical cables as required.
7. Engage the ST fiber optic connector of mat 1 onto one side of the cable-to-cable
connector. Turn the ST connector until the cable-to-cable receptacle tabs are aligned with
the ST connector slots. Further engage the ST connector and turn it until secured.
8. Engage the ST fiber optic connector of mat 2 on the other side of the cable-to-cable
connector. Turn the ST connector until the cable-to-cable receptacle tabs are aligned with
the ST connector slots. Further engage the ST connector and turn it until secured.
9. Repeat steps 7 and 8 in order to have the safety mats optically connected in series.
10. Gently pull the 2 inch sleeve tube for all safety mat cables through the rubber seal of the
cable gland. Ensure the sleeve tube is visible from both sides of the cable gland.
11. Install the plastic cap screw onto the cable gland and hand tighten to ensure proper
sealing.
For application help: see Warranty Information