TIMING CONDITIONS
The 8 ms minimum time difference between the two SMs inputs guarantees the
detection of a permanent short circuits of one of the SMs inputs. Physically, the 2
sensors must be separated so than someone cannot actuate both of them.
If a new transition of a sensor SM occurs during a muting sequence, the muting
sequence is immediately stopped to avoid the permanent muting of the safety
function. The relative position of sensors SMs and EMs define a minimum distance
between 2 successive moving objects.
In the conveyor mode, the object must interrupt the safety light curtain
detection beams, before releasing both sensors SMs and 6s max. after the
actuation of the second sensor SM.
Figure 2.4 : Example of an incorrect installation
t
< t < t
min
max
SM1
SM2
< 6 s
OSSD
OSDs
Muting
Protection
allowed
∆t = 50 ms
tmin = 8 ms / tmax = programmable from 1s to 8 s
The muting sequence starts 50 ms after both sensors SMs have been actuated. The
seconde transition of the sensor SM1 stops the muting sequence in progress and the
status of the module OSDs outputs is identical to the status of the protective equipment
OSSDs ouputs.