Honeywell SYA14 Series Manual page 555

Safety light curtains
Table of Contents

Advertisement

Selection of
Position of switches
the
ST3
maximum
timing tmax.
ST3-1
ST3-2
8 s
ON
ON
4 s
OFF
ON
2 s
ON
OFF
1 s*
OFF
OFF
(*) : settings factory settings
COINCIDENCE TIMING BETWEEN SMs SENSORS AND MUTING
DURATION
Select the tmax timing corresponding to the shortest muting duration ∆max
enabling the object transfer on a conveyor.
On a press, both SMs sensors must be activated within the following time
frame : 8 ms < t < 1s. The maximum duration ∆max of the muting sequence must
be set to 1 mn. These are the factory settings.
Failure to comply with these instructions could result in death or serious
injury.
2.4.3 EM inputs (end of a muting sequence)
Two auxiliary sensors may be necessary to stop a muting sequence. These two
sensors may be ultrasonic sensors, photoelectric controls, limit switches or
inductive proximity sensors. Correct operation of these sensors is monitored by
the muting module.
FACTORY SETTINGS
The muting module is set in the conveyor mode on delivery. In this mode, the
muting sequence stops when the first EM sensor switches
In the press mode, the muting sequence stops when the first EM sensor
switches off (for the selection of the press mode, refer to the chapter 2.4.1
Selection of the appropriate mode).
107004-15 EN FR26 ROW 0899 Printed in France
Corresponding muting durations ∆max
Press Mode
Conveyor Mode
60 mn
60 mn
4 mn
8 mn
2 mn
4 mn
1 mn
2 mn
.