Test input option

This fail-safe equipment is based upon a permanent self-checking principle which means that
its integrity does not rely upon the use of the test option. However, the test input may be used
to interface the equipment with the machine circuitry to check the correct operation of the Final
Switching Devices K1 and K2 when the equipment is not often triggered by frequent beam
occultations :
A test cycle can be triggered when closing an external NO test contact or when opening an
external NC test contact. The configuration of the type of external test contact (NO or NC
contact) is be done by setting a jumper located behind the emitter side cover. In order to
change the jumper setting, open the emitter by unscrewing the side covers and follow the
following indications :
EMITTER
Wiring diagram
Jumper position (see NOTICE)
Emitter
qq
q
FF-SPE
X
Emitter
(+)
C4
(-)
C5
50 mA / 20 Vdc
Test input :
Contacts status
TEST-CONTACT
De-activated
Activated
*Press the restart push-button if necessary.
After activation of the test contact, the NO contacts of the equipment (X1 and X2) are open,
the NC contact of the equipment is closed and the NO contacts of the FSD (K1 and K2) are
open.
NOTICE
1) On delivery, the equipment is configured for the use of a NO test contact.
2) The cyclic use of the test input is easier in the Automatic restart mode or in the start
interlock mode.
3) In the Automatic restart mode, it takes 140 ms for the system to restart after the test
contact is released.
For application help: call 1-800-537-6945
Jumper
location
Test NO test contact (Factory setting)
Receiver
A1
A2
B1
B2
C1
C2
C3
C5
NO contacts X1 and X2 NC contacts X1 and X2 NO contacts K1 and K2
Closed
Open *
Jumper position
C4
C5
Arc suppressor
(see relay supplier for best value)
R1
Hot
Neutral
R2
Hot
Additional Output
R1
R2
R1
R2
Power
Open
Closed *
Honeywell • MICRO SWITCH Sensing and Control 23
Installation
Jumper position
Test NC test contact
C4
C5
100 ms < t < 3,4 s
Machine control
Closed
Open *