Figure 4-1 Input Protection Interface For Trip Contacts - Siemens SINAMICS PERFECT HARMONY GH180 Operating Instructions Manual

Medium voltage variable frequency drive, air cooled 6sr5
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Description
4.1 Cabinet Details
Figure 4-1
If the drive exhibits excessive losses or reactive power, the NXG I/O digital output (M1-DOUT)
is opened and the dedicated NXG I/O digital output (IDO-15) is closed as a one-shot pulse
that latches the LFR coil. This action causes the Normally Closed (N.C.) LFR contact to OPEN.
MV IP Breaker Enable
The MV IP Breaker Enable contact
the drive input medium voltage up on the rare event of a secondary circuit fault.
● Contacts close = Permissive to close breaker
● Contacts open = Trip breaker
Failure to integrate this contact as specified may cause death, serious personal injury and
damage to the drive.
Terminal Blocks
The drive uses 8 mm, 600 V terminal blocks from the auxiliary input three-phase voltage (used
primarily for blower control). These terminals accept #8 - #22 AWG wire.
The single-phase control terminal blocks accept #12 - #22 AWG wire.
Auxiliary Voltage Transformer
The auxiliary voltage transformer steps customer-supplied three-phase auxiliary voltage down
to a single-phase 220 V for use with an NXG controller.
Note
Selection of Auxiliary and Control Voltage Supply
When Auxiliary and Control Voltage Supply Option is selected, control power will be supplied
by the customer's power source and auxiliary transformer will be installed.
20
Ratings PB4E-Stop:
600 VAC, 10 Amp Cont., 12 Amp make, 1.2 Amp break
Digital Outputs:
230 VAC, 1 AC
LFR N.C. Contacts:
30 VDC and 120 VAC, 10 A
100 VDC, 0.5 A
240 VAC, 7.5 A
Input Protection Interface for Trip Contacts
DANGER
must be integrated with input switchgear to deactivate
Operating Instructions, 07/2018, A5E42736645A_AB